Automatic Pre-Pump Strainers - Pump Protection

Automatic Suction Strainer Upstream Of The Pumps » PPS «

 

 

pps-automatic-pre-pump-strainer-img01.jpgPre-pumping filtration protects not only the pump itself but the entire pump filtration system such as cooling towers and heat exchangers.

 

By protecting these systems and their pumping operations from clogs and deterioration, Automatic Pre-Pump Strainer helps to significantly extend the life of the pump and the system and ensure more effective and efficient pumping.

 

AUTOMATIC PPS is specially designed to help keep pumps and their systems from becoming clogged by organic or inorganic debris, trash and solid dirt. The pump filtration system is connected to an outlet, which flows to the pump. The system is installed submerged in the water source (rivers, reservoirs, sea water, etc.).

   

 

 

Operation

As pumped water flows through the filter - organic or inorganic debris, trash and solid dirt are trapped on the screen. This prevents clogs and damage. In addition, pump and pump filtration system efficiency are increased and maintenance costs are reduced.

The filter screen is automatically self-cleaned by the continuous and adjustable rotation of the filter nozzles and spray. The trapped debris, trash and solid dirt are swept away from the screen.

 

 

pps-automatic-pre-pump-strainer-img02.jpg

Legend:

  1. Water Pump
  2. By-pass
  3. Manual Filter
  4. Rotating Flushing Sprayer
  5. Nozzles
  6. Stainless Steel Screen Surface
  7. Outlet to Pump
  8. Inlet for PPS Operation
  9. Outlet for PPS Operation
  10. Pressure Gauge
  11. Non-Return Valve
  12. Ball Valve
  13. Hydraulic Motor

 

 

 

Model

Inlet / Outlet Diameter

Recommended Flow Rate [up to]

1200 Micron

2500 Micron

inch

mm

m³/h

gpm

m³/h

gpm

PPS 1004

4

100

80

350

100

440

PPS 1006

6

150

150

660

190

840

PPS 1008

8

200

300

1320

380

1650

PPS 1010

10

250

500

2200

630

2780

PPS 1012

12

300

700

3080

880

3880

PPS 1014

14

350

1100

4840

1000

4400

PPS 1016

16

400

1400

6160

1380

6080

PPS 1018

18

450

1750

7700

2180

9600

PPS 1020

20

500

2200

9690

2750

12100

 

 

 

 

 

 

 

  • Recommended operating pressure: 2 - 3 bars
  • Minimal operating pressure: 1.5 bars

 

 

Upon request it is possible to deliver tailored, customised specifications

 

Automatic pre-filtration strainers are produced in a top technical and technological quality, and at the same time their installation, operation and maintenance are very easy. They are intended for a continuous operation.

 

 

If you require protection of pumps, please contact us and we will draw up, free of charge, a proposal to you.

 

 

High Quality Water No Matter Where It Comes From